Lowara Presfix Beta 280 Dual System (Max Fill Pressure 8 bar)

Lowara Presfix Beta 280 Dual System (Max Fill Pressure 8 bar)

Description

Lowara Presfix Beta MK 2 280 Dual System (Twin pump, Max Fill Pressure 8.0 bar)
Presfix Beta dual pressurisation sets bring the benefits of managing two independent systems
from a single unit. The unit contains two individual display screens, so each system can be controlled
and monitored separately providing both systems operate at the same fill pressure which should
generally, be the case as the fill pressure is based on the building static height.
All other set points can be independently set for each system.
All Presfix Beta Dual system units are supplied as two pump sets
Each pump is available to both systems, so each system has a duty and standby pump available to it.
If one pump fails, then the standby pump will be available to both systems.

Features;
Mains door interlocked disconnect switch, Auto/Manual/Off selector switch, Back lit digital display. Control panel section IP 54, MCB protected motors, Simple set point adjustment, Parameter lock, Remote inhibit, Delay start, Exercise regime, Break tank low water monitoring, Transducer controlled, High/Low pressure contacts for boiler/chiller interlock, Anti-bounce internal vessel 2lt electronically assisted, Isolating valves on each pump, Hours run for each pump, Automatic duty pump rotation with omission of tripped or failed pumps, Duty pump fail with auto change over to stand by pump.

LED indicators for:
Pump run each pump.
Pump trip each pump.
Low pressure.
High pressure.
Duty pump failed.
Excessive run time.
Break tank Low water.
Back lit display provides indication of power on.

Volt free contact for:
Pump run each pump.
Pump trip each pump.
High pressure.
Low pressure.
Excessive run time.
Break tank low level.
Duty pump failed.

Maximum fill pressure; 8.0 bar
Weight; 52Kg
Motor size; .75kWatts
Input current; 6A
Pre-fuse; 10A

Product Range Information

Lowara Presfix range of pressurisation equipment, Microprocessor Single and twin pump units
These units are designed to replace water that has been lost through system leakage and to maintain the system design fill pressure in sealed heating and chilled water systems in accordance with BS7074 parts 1, 2 and 3. & EN12828

All Presfix units provide safety circuits locking out the boiler / chiller in the advent of high/ low pressures occurring.
Expanded water is accommodated in membrane vessel/s that are supplied separately and normally installed alongside the Presfix unit.

Presfix Beta Mk2 “dual” pressurisation sets bring the benefits of managing two independent systems from a single unit
All Presfix Beta Dual system units are supplied as two pump sets and are available in three ranges,
2.8 bar, 5.5 bar and 8.0 bar fill pressures.

Presfix Beta MK2 pressurisation sets are available as single or twin pump units, and available
All Presfix Beta Dual system units are supplied as two pump sets and are also available in three ranges, 2.8 bar, 5.5 bar and 8.0 bar fill pressures.

Mini Presfix pressurisation sets are available as single or twin pump units, and are available
In two ranges, 2.8 bar and 5.5 bar fill pressures.

Micro Presfix pressurisation sets are available as single or twin pump units and have a maximum
fill pressure of 4 bar